BURDEN BOX FOR CT:
Available in four sets
Rated current | Power Factor | Burden | Accuracy of adjustment |
5 A | Unity | 2.5, 7.5, 15, 30VA | Within i) + 3% of burden value. ii) + 2 electrical degree for angle. |
5A | 0.8 lag | " | " |
1A | Unity | " | " |
1A | 0.8 lag | " | " |
Burden Box of other Burden & Accuracy class are also manufactured as per customers? requirement.
BURDEN BOX FOR PT:
Available in four sets
Rated voltage | Power Factor | Burden | Accuracy of adjustment |
110V | Unity | 5 to 200VA in steps | Within i) + 3% of burden value. ii) + 2 electrical degree for angle. |
110V | 0.8 lag | " | " |
63.5V | Unity | " | " |
63.5V | 0.8 lag | " | " |
Burden Box of other Burden & Accuracy class are also manufactured as per customers? requirement.
TYPE: CBANT01
SYSTEM FEATURES:
DATA ACQUISITION FEATURES:
The operations will be for single break in OFFLINE mode. MAKE, BREAK and O-C-O sequence operation will be provided.
Parameters RECORDABLE:
DIGITAL DATA CHANNELS AVAILABLE:
Analogue Date Channels
Marked channels are normally required and as per our current plan further channel can be extended with the software change only.
SPECIFICATION:
Timing : A period of 100ms nominal.
Trigger : Closure of external voltage free contact to start calibration.
Power Supply: 230 V, 1 Ph, 50Hz.,AC.
Series: CTECAHV2; Type: 001K01A
The Test Set will be capable of measuring the following parameters of a CT based on Voltage Comparison Method.
i. Magnetising Characteristic
ii. CT Ratio
iii. Polarity
Input: 230 Volts, 50Hz., single phase AC.
Output: Continuously variable in 4 ranges.
Power supply Transformer is isolation type with electrostatic shielding.
Duty: 5 mins. ON, 15 mins. OFF.
Metering: 4? digit Digital voltmeter used for measuring primary & secondary
Voltage: 4? digit Digital ammeter used for measuring excitation current.
--------------------------------
Series: CTECAHV1; Type: 003K200m
Input: 230 Volts, 50Hz., single phase AC.
Output: Continuously variable in 4 ranges
and for AC High Voltage Test mode 0 to 3000V at 0.2 A Max. Tripping circuit at 50mA, 100mA & 200mA provided.
Duty: 5 mins. ON, 15 mins. OFF.
Metering: 4? digit Digital voltmeter used for measuring primary & secondary
Voltages: 4? digit Digital ammeter used for measuring excitation current.
---------------------------------
Series: CTECAHV1; Type: 005K03A
Input: 400/415 Volts, 50Hz., two phase out of three phase AC.
Output: Continuously variable from 0 to 5KV for AC High Voltage Test mode at 3A Max.
Tripping circuit at 500mA, 1A, 2A & 3A provided.
Duty: For 3A, 5 mins. ON, 15 mins. OFF.
For 2A, 30mins. ON, 30 mins. OFF.
For 1A & 500mA continuous.
Metering: 96-sq. mm. moving iron type voltmeter generally connected to the LT side and scaled in KV. 96-sq. mm rectifier type milliammmeter.
Microcomputer based version of this set is also available.
Input : 230 Volts, 50Hz, single phase AC.
Output: Variable from 0 - 1000V AC, 1 phase, in 3-ranges i.e.
0 to 10 Volts AC at 2 Amps Max.
OR
0 to 100 Volts AC at 2 Amps. Max.
OR
0 to 1000 Volts at 1 Amps Max.
Duty: 5 mins. ON & 15 mins. OFF.
Metering: Digital Frequency Meter - 1no.
3 1/2 digit Digital Voltmeter having 3 ranges-1no.
3 1/2 digit Digital Ammeter having –1no.
The set is provided with zero-start interlocking, overload and short circuit protection.
The Set also is provided with surge and harmonic suppressor to get quality AC voltage, which is a basic requirement for this.
The set is a nice looking portable sheet steel cubicle.
The set can also be available in automatic mode.
IBL make DC high voltage vacuum test set is suitable for testing the integrity of the vacuum circuit breaker
Input : 230V, 50Hz, single phase AC.
Output : Continuously variable from zero to max. rated DC output voltage.
Type X, denotes L if the set is used for laboratory purpose & P if the set is used for testing at sites. | Output voltage | Current capacity | No. of units , if the set is used for laboratory purpose | No. of units , if the set is used for testing at sites. |
DHVVAC30X | 0 to 30KV DC | 1mA max. | Single (HV supply unit) | Two (HV supply & control measuring units) |
DHVVAC60X | 0 to 60KV DC | 2mA max. | Two (HV supply & control measuring units) | Two (HV supply & control measuring units) |
If the Test Set is used for Laboratory purpose, then Test Chamber may be provided at extra cost.
Duty Cycle: Intermittent ie. 5 mins. ON, 10 mins OFF. However, test sets of continuous or other duty cycles can also be manufactured at extra cost.
Protection: Overload & short circuit provided. Zero start interlocking along with Overvoltage alarm & indication are provided.
Metering: DC high voltage measured by means HV resistor chain along with micro-ammeter. Milliammeter measures the leakage current. Digital meters may be provided at extra cost.
Discharge rod: A discharge rod is provided with the set.
CT TEST SET
A] CT TEST BRIDGE:
This test bridge is suitable for testing current transformer having secondary current of 5A and 1A.
Input Voltage : | 230V, 50Hz. , 1 phase AC. |
Secondary Current : | 5A and 1A. |
Phase Angle Error Range : | 0 to + 20 minutes on x1 range 0 to + 100 minutes on x5 range 0 to + 400 minutes on x20 range |
Ratio Error Range : | 0 to + 0.5% on x1 range 0 to + 2.5% on x5 range 0 to +10% on x20 range |
Polarity Check : | Polarity indicated by lamp with "check" position selection. |
Ammeter : | One digital ammeter to indicate the injected current in %. |
Detector : | A built-in detector of electronic type. |
Test Bridge having secondary current of 5 Amps. only is also manufactured.
B] burden box:
Rated current : | 5 Amps., 1 Amps. |
Power factor : | 0.8 lag, unity |
Burden : | 2.5, 7.5, 15 and 30 VA. |
Accuracy of adjustment : Within i) + 3% of burden value.
ii) + 2 electrical degree for angle.
C] precision current TRANSFORMER: 5 amps. & 1 amps.
Primary : Wound : | 5, 10, 15, 30 & 50 Amps. |
Bar : | By winding number of turns through center hole, following ranges can achieved - 100, 200, 300, 400,500, 600, 1000, 1200, 2000A. |
Secondary : | 5 Amps. & 1 Amps. |
Burden : . | 5 VA |
Accuracy : | Class 0.1. |
Voltage grade : | 600V |
Termination : | The wound primary & secondary will be terminated on suitable brass studs duly marked. |
Construction : | The complete transformer will be housed within a polished wooden case provided with center hole & carrying handle. |
PT TEST SET
A] PT TEST BRIDGE:
This test bridge is suitable for testing potential transformer having secondary voltage of 110V and 63.5V.
Input Voltage : | 230V, 50Hz. , 1 phase AC. |
Secondary voltage : | 110V and 63.5V. |
Phase Angle Error Range : | 0 to + 20 minutes on x 1 range 0 to + 100 minutes on x 5 range 0 to + 400 minutes on x 20 range |
Ratio Error Range : | 0 to + 0.5% on x1 range 0 to + 2.5% on x5 range 0 to +10% on x20 range |
Polarity Check : | Polarity indicated by lamp with "check" position selection. |
Voltmeter : | One digital voltmeter to indicate the secondary voltage. |
Detector : | A built-in detector of electronic type. |
Test Bridge having secondary voltage of 110V only is also manufactured.
B] burden box:
Rated current : | 110V, 63.5V |
Power factor : | 0.8 lag, unity |
Burden : | 5 to 200 VA in steps. |
Accuracy of adjustment : Within i) + 3% of burden value.
ii) + 2 electrical degree for angle.
C] precision potential TRANSFORMER
Primary : | 33KV or 11KV |
Secondary : | 110V / 63.5V |
Burden : | 5 VA. |
Accuracy : | Class 0.2 |
System voltage : | 33KV effectively earthen. |
Termination : | HT & LT on suitable insulated terminals. |
Type : | Cast Resin Air Cooled with carrying handle. |
D] precision potential TRANSFORMER
Primary : | 400, 660, 2200, 3300 or 6600V by series parallel combination. |
Secondary : | 110V |
Burden : | 5 VA. |
Accuracy : | Class 0.2 |
System voltage : | 6.6KV effectively earthen. |
Termination : | HT & LT on suitable insulated terminals. |
Type : | Cast Resin Air Cooled with carrying handle. |
Precision Potential Transformer of other Voltage, Burden & Accuracy class are also manufactured as per customers? requirement.
(Type: UONT100A)
This Test Set is capable to measure low resistance like switch contacts, breaker contacts, busbar splices, joints, fuses, low inductive windings etc. by circulating high value of D.C. through the contact/junction and measuring D.C voltage drop (4 terminal method) which, sent to instrument amplifiers , thereby being displayed on resistance meter.
Technical Features:
Resistance Range | Resistance meter reading display | Resolution | Test Current |
200mW | 199.9 | 0.1mW | 100A |
2mW | 1.999 | 1mW | 50A |
20mW | 19.99 | 10mW | 20A |
200mW | 199.9 | 100mW | 10A,5A |
Input: 230 Volts + 10%, 50 Hz., single phase AC.
Accuracy: + 1% of reading.
Metering: 2-nos., 31/2 digit LED module for resistance measurement & current measurement.
Protection against overload & short-circuit.
This is a portable DC Injection Set suitable to observe millivolt drop across low resistance elements, contacts, switches, D.C. motor commutator segments etc.
Input : 230 volts, 50Hz, 1Phase, AC upto 300A.
400/415 V, three phase, 4 wire, 50Hz. , AC above 300A.
Output : Continuously variable from zero to maximum rated current required.
Series: MVDTXPYYU;
X denotes single phase input (1) or three phase input (3);
YY denotes DR or OC i.e. either the transformer will be air-cooled or oil cooled type.
U denotes no. of units ? either one (1) or two (2).
Type: Y1Y1Y1AZZV;
Y1Y1Y1 denotes the maximum current capacity in Amp.
While, for Y1KAZZV; Y1 denotes the maximum current capacity in kAmp.
ZZ denotes the open circuit voltage rating.
We manufacture these sets in wide range up to 3KA and of various capacities.
Duty Cycle : 5 minutes ON & 10 mins. OFF. Sets of other duty cycle can also be manufactured at
extra cost.
Units : 1 unit upto 500A.
2 units above 500A upto 3000A.
Transformer : Air-cooled upto 1000A. Oil cooled above 1000A upto 3000A.
Step down rectifier transformer with full wave rectifier bank consists of 4 nos. silicon diodes along with surge suppressor.
Protection against overload & short circuit is provided. ?Zero Start Interlock? protection is also incorporated.
Metering: Analog millivoltmeter, voltmeter & shunt operated ammeter. Digital meters can be provided at extra cost.
One set of probes to measure millivolt drop between two points of test sample is provided.
type: pdnt02
This Test Kit is used for non-destructive means of assessing the quality of high voltage transformers, motors, cables etc., which are used in generation & distribution of electric power.
The basic system consists of-
Input : 230volts, 50Hz., single phase AC.
Measuring Range: 0 to 5,50,500,5000pC in different switchable ranges.
Discharge pulses can be detected and measurement can be done in analog scale as well as in PC.
OPTIONAL AT EXTRA COST:
40 kV AC high Voltage measuring system
Auxiliary Supply Voltage: 230 Volts, 50Hz, single phase, AC.
Range: 0 - 40 kV AC
Metering: 31/2 digit digital panel meter.
precision current TRANSFORMER: 5 amps. & 1 amps.
Primary : | Wound : 5, 10, 15, 30 & 50 Amps. |
Bar : | By winding number of turns through center hole, following ranges can achieved - 100, 200, 300, 400,500, 600, 1000, 1200, 2000A. |
Secondary : | 5 Amps. & 1 Amps. |
Burden : | 5 VA. |
Accuracy : | Class 0.1. |
Voltage grade : | 600V |
Termination : | The wound primary & secondary will be terminated on suitable brass studs duly marked. |
Construction : | The complete transformer will be housed within a polished wooden case provided with center hole & carrying handle. |
Current Transformer of other Current range, Burden & Accuracy class are also manufactured as per customers? requirement.
precision potential TRANSFORMER
Primary : | 33KV or 11KV |
Secondary : | 110V / 63.5V |
Burden : | 5 VA. |
Accuracy : | Class 0.2 |
System voltage : | 33KV effectively earthen. |
Termination : | HT & LT on suitable insulated terminals. |
Type : | Cast Resin Air Cooled with carrying handle. |
precision potential TRANSFORMER
Primary : | 400, 660, 2200, 3300 or 6600V by series parallel combination. |
Secondary : | 110V |
Burden : | 5 VA. |
Accuracy : | Class 0.2 |
System voltage : | 6.6KV effectively earthen. |
Termination : | HT & LT on suitable insulated terminals. |
Type : | Cast Resin Air Cooled with carrying handle. |
Potential Transformer of other Voltage, Burden & Accuracy class are also manufactured as per customers? requirement.
"ntpl" Digital Time Interval Meter is suitable for measuring, "switching" time of relays, "trip"(actuation time) time and "ON" (recovery time) time of circuit breaker, fusing time of fuse elements, travel time of switches.
Type: NTT4D
Input Power Supply : | 230 volts, AC + 10% at 50 Hz. |
Display : | Four-digit display with 7 segments LED |
Range : | 9.999secs. OR 99.99 secs |
Accuracy : | + 1 % |
Type: NTT3ch4D
The above time interval counter is particularly suitable to check simultaneous operation in three different channels.
Range : 999.9msecs. Or 9.999secs.
All the other technical features will be same as Type NTT4D